Circuit Behavior
This command determines whether the circuit stays open or closed when
no alarms are active. The opposite behavior occurs for an active alarm con-
dition. Default is normally open. Choose normally open if you want the
Alarm Ou
tput data logger to leave an electrical device OFF unless an
alarm condition occurs. Choose normally closed if you want the Alarm
Output data logger to leave an electrical device ON unless an alarm condi-
tion occurs. Normally open mode conserves console or Envoy battery
pow
er.
Note: This command only affects the output tab that is currently selected.
Default
Press this button to restore the data entries to their default values. You must
stil
l hit OK to save the settings in the data logger.
Output
Select the appropriate tab (Output 1 - 4
) to configure the alarm settings for
each output.
For each output, select the first parameter you want to test. (If using the
“Minus” check type, you
will need to select a second parameter after you
select the Minus check type.)
Then, select what type of test cond
ition you want to check it against:
•A G
reater Than or = (or high alarm) checks whether the current value
is greater than or equal to the value entered.